Is builders foam fire stopping?

  • Every seal labelled and photographed
  • BM TRADA / FIRAS-certificated contractors
  • Written price before any work
Get a price

We reply with a written price.

We use these details to reply to you. See our privacy notice.

No. General purpose expanding foam from a builders merchant fills gaps and insulates. It is not tested as a fire seal, and on a survey it counts as an open gap.

Fire-rated foams do exist. They are only a fire seal when fitted to the maker's tested detail: the right gap size, the right wall or floor, the right services, the right depth.

A black corrugated conduit entering a wall just below a concrete soffit, with a lump of white foam round it
A black corrugated conduit entering a wall just below a concrete soffit, with a lump of white foam round it

How to tell them apart

Look at the colour first, but do not trust it. Fire-rated foams are often pink, red or grey. General foam is usually cream or yellow. Some general foams are coloured too.

Look for a tag. A seal with a tag and a record is checkable. Foam with no tag is not.

Look at what it is round. Foam round a plastic pipe on its own will not close the hole when the pipe melts, whatever the foam is.

Look at the size. Many fire-rated foams are only tested up to a certain gap width.

The photo on this page

A corrugated plastic conduit goes into a wall under the soffit, at a school block we worked on. A lump of white foam is pushed in round it. No tag. On the survey list it was a gap to be sealed.

What happens to it

Foam of unknown type is cut back out of the hole. The gap is then sealed to a tested detail. For a plastic conduit that might be a wrap or a mastic detail tested for it.

Tag. Photo. Line in the record.

Want a written price for your building?

Give us the postcode, the use of the building and the number of floors. A survey page or a few photos of the gaps lets us price it faster.

Call 0121 816 0200Get a quote